HomeMy WebLinkAboutDocumentation_Planning and Zoning_Tab 2_12/20/2018 (5)r �T `
Tequesta Fire Rescue
Fire Hydrant Inspection Report
Hydrant #: �~y Date: Inspector:
Location: U5 14gY / A).
Static Pressure: Discharge Used (circle one)2'/2" 4"
Pitot (Flow) Reading:
Residual Pressure:GPM: / d f;
71
ITEM PASS/FAIL REPAIRS NEEDED
A) Height
The center of a hose outlet must be at least 18" above final grade.
B) Paint
C) Caps
D) Chains
E) Clearance
All vegetation, and other obstructions are at least 3' away from hydrant.
F) Operation Nut
G) Reflector
Co a ts:
jx
fc g ypeAt( c{s �1rL►y n,(� � �c c�-3�
General guidelines:
- Prior to conducting hydrant flow test; notify the Water Dept. (575-6234).
- The test hydrant is the hydrant that the static and residual are taken at. There
must be at least a 10% drop in the static pressure after opening the flow hydrant.
- From an accuracy standpoint it is preferable to use the 2'/2" outlet rather than the
steamer outlet.
- To determine gpm discharge from a hydrant use the formula:
29.7xDzn.9
FIRE HYDRANT FLOW TEST
APPLICATION
REQUESTED BY:
Amy Galvez c/o Simmons and White
ADDRESS: 2581 Metrocentre Blvd. West, Ste. 3 West Palm Bach FL 33407
PHONE NUMBER: 561-478-7848
FAX NUMBER: 561-478-3738
EMAIL: amy@simmonsandwhite.com
PROJECT ADDRESS: 691 and 19626 N. US. Highway 1 & 3471 Inlet Court and 3486 Canal Ct.
FIRE FLOW AREA, if applicable S � l�:' sq ft.
(Per definition on Fire Flow Information Sheet) -
CONSTRUCTION TYPE: (use Florida Building Code type) V Qf, ef) 4c d
TYPE OF PROJECT
� tin �f- �' u.ns�►�
0 Residential Building V('
❑ Commercial Building --- i1lA 3
V Fire Protection System
IS THIS PROPOSED CONSTRUCTION PROJECT EQUIPPED WITH A FIRE I
SUPPRESSION SPRINKER YSTEM?
I� YES Q G - A-, q%1
NO',• Q ( d 0
YOUR RESULTS WILL BE FAXED OR EMAILED TO OU IF REQ STED
Submitted by:
Name: (print) Amy Galyez Signature:
Company Simmons and White Cell #
Attach the Fire -Rescue Department approval letter and a copy of this worksheet
with the building's permit application. _h b+ �8_� SLLb fttfQ - � �� (�� /10,-✓
I- V 0 i 9 4-0- P (k. r 64AIV rWI&
FIRE FLOWS
The effective date for this requirement was January 1, 2013.
The Florida Fire Prevention Code (FFPC) now requires that a newly constructed or
substantially improved buildings, including one and two-family homes, must be built within
the parameters of the fire flow capability provided to that property. These flows and
durations are important to ensure that there is a sufficient water supply to extinguish a fire
in the building and to keep it from spreading to nearby buildings.
The Code requires a minimum of 1,000 gallons per minute (GPM) fire flow for duration of
two hours for homes having a fire flow area of 5,000 square feet or less. Fire flows
commercial construction and homes with a fire flow area exceeding 5,000 square feet
shall not be less than that specified in the Florida Fire Prevention Code, NFPA 1, Chapter
18, Table 18.4.5.1.2. This table calculates the needed fire flow (GPM) based on the fire
flow area and construction type of the building.
If the size of the proposed building or home design exceeds the water system capabilities,
the Florida Fire Prevention Code provides the owner with a the means for meeting and/or
reducing the fire flow requirements. These options are listed below and may be
incorporated in the building design either individually, or in combination with others.
DESIGN OPTIONS
• A 50% reduction in the required fire flow can be attained with the installation of a
fire sprinkler system. Installation requirements can be found in the Florida Fire
Prevention Code 2010, NFPA 13D or the Florida Building Code 2010 Residential
Chapter 29, Section P2904. The reduction shall not reduce the required fire flow
to less than 500 gallons per minute (GPM).
• A 25% reduction in the required fire flow can be attained for homes with a fire area
of 5,000 square feet or less when separated from other buildings by a minimum of
30 -feet.
• Based on Table 18.4.5.1.2 in NFPA 1, reductions in the required fire flow can be
attained using different construction types and/or fire resistive materials.
• Adding a fire hydrant and/or increasing the size of the water main distribution
system to provide for a greater gallon per minute (GPM) flow.
• The Fire -Rescue Department will accept any other recognized fire flow calculation
method as an equivalency to the FFPC, i.e. Insurance Services Office (ISO)
Method, Iowa State University (ISU) Method, Illinois Institute of Technology
Research Institute Method.
SIMMONS WHITE
ENGINEERING I PLANNING I CONSULTING 1 SINCE 1962
2581 Metrocentre Blvd. West, Suite 3
West Palm Beach, FL 33407
561.478.7848 1 561.478.3738
www.simmonsandwhite.com
TO Tequesta Fire Rescue
357 Tequesta Dr.
Tequesta, FL 33469
LETTER OF TRANSMITTAL
DATE 9-20-18
NOB 17-137
ATTENTION
RE: Pelican Square
1
$131.61 fee
❑ Submit
VIA: courier
WE ARE SENDING YOU E Attached El Under separate cover via the following items:
❑ Shop Drawings ❑ Prints ❑ Plans ❑ Samples ❑ Specifications
❑ Copy of letter ❑ Change Order ❑
COPIES DATE
NO. DESCRIPTION
1
Fire Hydrant Flow Test Application + Site Plan
1
$131.61 fee
❑ Submit
copies for distribution
❑ As Requested
❑ Returned for corrections
❑ Return
corrected prints
THESE ARE TRANSMITTED as checked below:
❑ For Approval
❑ Approved as Submitted
❑ Resubmit
copies for approval
® For your Use
❑ Approved as Noted
❑ Submit
copies for distribution
❑ As Requested
❑ Returned for corrections
❑ Return
corrected prints
❑ For Review & Comment ❑
❑ FOR BIDS DUE ❑ PRINTS RETURNED AFTER LOAN TO US
REMARKS
Please let me know if you need any additional information. Thank you!
COPY TO SIGNED
NAME vez, .
yEt
y e tt3�'8g
Y
a