MEMORANDUM:
TO: Thomas G. Bradford, Village Manager
FROM: Thomas C. Hall, Water System Manager lib
DATE: December 3, 1992
SUBJECT: Diesel Fuel Storage
As you are aware in this year' s budget, the Water Department
has allocated $30,000 for upgrading our Diesel Fuel Storage tank at
our Water Treatment facility -on Old Dixie Highway.
Due to the strict regulatory requirements now in place, we
must remove our old underground tank as we did behind Village Hall
and replace it with a unit that meets today's standards.
We intend to increase our fuel storage capacity from 500 to
1, 000 gallons, thereby allowing us to have an increase in fuel
availability in times of emergency. Present tank capacity only
provides sufficient fuel for our plant emergency generator to
operate continuously for just under five days. This new tank will
increase our emergency operation capability to almost ten days as
well as being an additional supply source for our portable
generator serving• our wellfields.
On October 20, 1992, specifications for the above tank were
mailed to the . attached contractor list requesting formal Bid
Quotes. A Bid Tabulation is attached. I would like to recommend
that the Village accept the quote from Glasgow Equipment Service,
Inc. in the amount of $13, 845.00. This company also performed the
previously mentioned tank removal and installation behind Village
Hall .
Please place this item on the Council agenda of December 10,
1992 for approval .
TCH/mk
Attachments .
•
Rv".,-4,1 P7ner
1, 000 GALLON DIESEL TANK
CONTRACTOR LIST
BID QUOTE
Glasgow Equipment Service, Inc.
1750 Hill Avenue
Mangonia Park, Florida 33407
Phone: ( 407 ) 842-7236 FAX: ( 407 ) 842-7402 $ 13, 845.00
PIECO, INC.
8105 W. 20th Avenue
Hialeah, Florida 33401
Phone: (305 ) 558-0440 FAX: (305 ) 362-0820 $ 20, 926.84
Olympic Industries, Inc.
P. O. Box 770
Palm City, Florida 34990
Phone: (407 ) 286-9319 $ .22, 445.00
Atec Associates, Inc.
3555 Fiscal Ct. Suite 9
West Palm Beach, Florida 33404
Phone: 844-1166 FAX: 844-7659 $ 14, 248.00
Missimer & Associates, Inc.
600 Sandtree Drive, Suite 101
Lake Park, Florida 33403
Phone: 775-6612 FAX: 775-6615 $ 26,456.00
Hydrocarbon Monitor & Environment
8414 South U. S. Highway 1
Port St. Lucie, Florida 34952
Phone (407 ) 468-4611 FAX: 489-5830 No Bid
Slater. Corporation
4700 S.W. 51st St. , Building 202
Davie, Florida 33314
Phone: . (305 ) 791-0336 FAX: 791-0650 No Bid
Underground Tank Specialties
5770 N. Military Trail
West Palm Beach, Florida 33407
Phone: 686-4223 FAX: 640-0224 No Bid
r �
VILLAGE OF TEQUESTA
L. ti, ' WATER DEPARTMENT
rPost Office Box 3474 357 Tequesta Drive
' ' Tequesta. F orida 33489-0474 • (407) 575-8230
October 20 , 1992
Glascow Equipment Service , Inc .
1750 Hill Avenue
Mangonia Park , Florida 33407
RE: Formal Quotation fdr 1 ,000 Gallons Convault Fuel Storage Tank
Dear Contractor :
The Village of Tequesta is requesting formal quotes within fifteen
( 15 ) days for the following:
o Provide all . labor , equipment and materials to remove and
properly dispose of one ( 1 ) 550 gallon steel underground Diesel
Tank .
o Furnish Organic Vapor Analysis testing on surrounding soil and
water .
o Provide D .E .R .M . and customer with written report . Backfill
the excavation with clean fill and compact to finished grade .
o Provide all labor , equipment , materials engineering ,
certifications , permits and fees to construct an 8 inch x 12
ft . x 6 '6' reinforced concrete slab . On the slab , furnish and
install one ( 1 ) new 1 ,000 gallon above ground Convault Fuel
Storage Tank .
o Include with tank all fittings , vents , overfill and spill
containment , fuel gauge and 20 year manufacturer 's warranty .
Vendor must also supply verification of tank approval from all
regulatory agencies having jurisdiction and tank must be UL
approved .
o Install double wall fiber glass piping from the tank to
existing building and transfer of fuel from old tank to new
tank .
Contractor must be State Certified as a pollutant storage systems
specialty contractor and be registered with the Village of Tequesta .
It is realized that any excessively contaminated soil must be
removed and properly disposed of at an additional cost .
,J 0 L/o: . >z-
i
- G
Should you have any questions , please contact the undersigned at
575-6230 . Please direct your correspondence to my attention .
Sincerely ,
•
•
Thomas C . Hall
Water System Manager
TCH/mk
I
r
t 'i+V`
SIDE VIEW int
�� �, v
TOP VIEW �. � �,
.,,,,t...,,o,,,,;::„,„%‘..,
7:GALLON U.L.LISTED OVERFILL CONTAINMENT VENT EMERGENCY Millie. 11 MUill® t r ., d ��•
dr ,
4" NIPPLE -,WITH INTERNAL DRAIN AND POSITIVE SEAL f NIPPLE i
111
f 1 NIPPLE o ollira81111111. '
6"Emergency Vent 2 # u '
ø27;=ll
O THE LEADER IN AE�OVE-GROUND FUEL STORAGE,•
1.
Leak Detector Tube 0
80001bs. �® 3,q„
D250 Gallon 12000 lbs. - . -
500Gnllnn ,2000lbs. CROSS SECTION - , - " _ .. -0500 Gallon 18000 lbs. '��� - _ . ..
1000 Gallon 18000 lbs. '®�� �'• . b ?;o; .I • _ -
D1000 Gallon 30000 lbs. ®�® - - - - , - - `
2000 Gallon 30000 lbs. I —P y - STEEL TANK i i as^I , - • - . ` - - n ;''''
S OOO Gallon 51000 lbs. 1.111111.. fl�Xi• -ii
INSUlATION'I.750"1 i _' •
�Xi ONES I30 MILL I" " - k
WIRE MESH i 11') r - k' - '
- CONCRETE 16,0"1 1 N ,y „w•
At last there is an environmentally safe and practical � r _ **� "
r
alternative for storing petroleum based products: Con- � .,
'a � ,
Vault's complete aboveground vaulted tank and fuelin s s- we " 4 .,d a
9 Y
tern. Constructed of steel and housed in an attractive con- • �* . "f,. wi`�= '># :- t
Crete vault, the unit offers secondarycontainment =' eft `: f s } r. '
state-of-the-art, cost-efficient way to meet your storage -` a-'�. 4 ter, . �q t ' "};
needs.
`(t �i ` r t ,.s+ *e � : `�,„
aw r • k' r- a : ''r, ��i ^r t5 r • r ..4 , . S
e '�' P �^� -. it �, •r"f '#J'wa �. r♦ • n, .,. tG?- 1 " a t:.
Put the storage tank of choice to work fOryou — _,. "u � , .. �,. ; ` ',r • a e ,• a, ,.
ConVault. U.S.PATENT'#4,$26,644;#4,9Dal,235;#4,934,122;#4,963„082; ,•� -- , .
•
#4,986,346(OTHER ti.S, FOREIGN PATS.PEND.) ° _ W -'�` ., F;'
Y
K r
'1.6
• z,s a t r--
•
m r -. ,L 3d `''I' . ',, 1.f' t l:r y r +" 4 _ 3'L. T '..et - - :'3.. a`s_w„ -� f '^ , '7.
•
1_ ' 1a 4,k n a' a a s`t"777 `' -�' ,9' 4= E- -,1 11 - P s �944 4
tt fib .0;i 1= " :d) • I! _ i, d I - r J A ^�
r � I FaO IDA iKd rdtl H �fT _ • ' 3 <;.1.,i':::;;;;.,;;. ...r,-;.,,..44.;,,,,,,,;;;.1:
1vstaiu tQ4JY�ilTtY'p ;;;;:::,4:::r*:°::!,f,C4stlt,.:7:..);':;
�Jr A Y
� F4Qfi1�A§'
w
x
° w ref s' -'
.,. ': ,
MFO. IN W/LOW000 BY I. -:#� ,,,v*. ," x*.1, `. _ - - - 3 s "rh "°" 'M: 3.P
Technical information with reference to '°"*' o-- �.oe'�
C results t tanks and various test CO NVAU�� ,. . '* -.-"' '`�,"�' :. - - '= m ... W. al, 0.•
can be obtained by writing Con- :. """ ��'q''� a .�.'r""'� -'•� ` �' � •n
Vault. Always consult local fire and °^' .„T- .*nY,� ':-r � ';_ '�°; �'°'�,,,'=«*' 3 .- `'1 ''s"` ,‘-tiAa" ,
'W` err , a " r ,i 4 «. .
building codes before installinga Con- **mow••-!�',�- ' ^'w-"^�� "' "� ��r '' -
Vault tank since environmental and rw.-...� s s. "�'°^._ ' rs� ' -M'*
safety regulations can vary between f �- ., k "R:'-- --a,,, . r t - e s"' ` '"' .rv��..�d„ry�
jurisdictions. Qc . :,,- _..-.. '� _ sc• -
,. _ - - --"''�- •, '�'.�¢
7-800-642-154® �
743,
"a"jr .ir'" .„..."'�'"e""� ^,:??x,,r,.,�r ;, ,r, s.- -& a"� C ma's x
t ` y ? r: cam , .• c a y - - Z# �s r�
.€ � �� to - ..4-g""'",w, ,.x=o
P.O. Box 238 • 1410 Industrial Drive • IA9ildwtood� Florida 34785-0238 ,,. - :-. ..•, 14 ` ,,1�; . e4, ---,- •-: , ;:. ,. -..
Phone �804) 748-6462 • (800) 642-1540 or,
FA)( I904) 748-6820 % '• '" �"
I.
'*z" { ` .a ,F; ,• •c;x a�` ... '^- ",a °J.•�:f• "` r a s" ..
y. w«,.^• -it ^'rr. ..wr , - - "�� 'a, `Tw '3's `� p
.— 'Gvk'wry�3...l„-., 'iF"t eo '4-y` ' , _ r "',S' S' 1 +.n_ ^F M
I t'
T I - r'1 ■ M 174'r },$,, 41Z,
C C . m . , V LiIt : 1 - ;r g':R �g N/.'' �".`f.� . i7 t-- --
-
R ) ter t NI l,1 2 i.ii."
FORAS IiJISITIVE Iu*JVIRDDNMENT - ° St
a. ¢ , 'k
,_C•HI fit. ,I* 1-- -1F:5- . 1 crVeit
C8V.t4bL1=y Bltt-6 N�OI4IDA
THE i ,x- -6 .
CONVAULT
ADVANTAGE �, Y Ili
3. ib: -,
,
ttritt.tz'1414." tot
DESIGNED FOR VALUE .°
■The ConVault storage system often costs less than half ; * .: ' , r z .
as much as comparable underground installations. The ` " '`'
elimination of system design engineering alone can pay for '' r�
the complete ConVault fueling system. Tank capacities . `� ' `' � THE ABOVEGROUND
range from 125 gallons to 5,200 gallons and can be mani- SOLUTION TO THE
folded for higher volumes. UNDERGROUND PROBLEM
• ConVault tanks have a long life; each comes with a
standard 20-year warranty. A 30-year warranty is / 1
■ Nationwide interest in the preservation of our envir-
o• nment has prompted all levels of government to issue
optional. �:,
f ' _ � <" 3 strict guidelines for the installation,operation and rem-
■ ConVault tanks are self-contained and portable. This oval of underground storage tanks(UST's).As a result,
b
allows for tank relocation or resale as your businessk .. -.. . ...; z ="` g
owners may a faced with expensive upgrades,testing,
requirements change. _ _ monitoring equipment and pollution liability insurance to
• ConVault's complete fuel storage and dispensing sys- comply with these regulations.In the event of a leak,the
tern is a finished unit when shipped. Units are manufac- actual costs for soil and groundwater clean-up can be
tured under strict quality control standards,with no need - 5 catastrophic.
for excavation, painting, assembly or completion. Addi- "`�� ray ''+ ���
�,,� t� � • ConVault's innovative vaulted aboveground storage
tional expenses are limited to freight, the cost of a con- -," ',,I . h',t�' t„ a'' � ��' '''T " - ' tanks are the proven solution for these problems. The
crete pad and electrical service if desired. • Con Vault patented system is designed for safety and
■ Leasing programs are available which offer flexible and ,, • value while complying with environmental and fire code
attractive lease-to-own options for both commercial and regulations.
government users.
MEETS GOVERNMENT, ' tti"
ENVIRONMENTAL AND FIRE
SAFETY REGULATIONS y ;, '4 1.7, F-
■ ConVault tanks meet applicable safety requirements 5w �, K y- ' r , r; ` � � " :r' '
Y(,"i �iM �4,y • • 4 .�� U' jj yA j�/I£ a i L � f S� �
for secondary containment, leak monitoring, and spill and � �� ��� o� ,?� - �, �,�: r 1 ;� -.
overfill protections. .. �r:.;��,-'`��,. '� '(mot ..l n�-''•� �,� ,�f� �r-� 'a� rs .>tr�, �iz � �_f7 �
{�-+. r/a' � $ d y'l f ' .,. T '4 ,�jt r7; f,;. r!�
■ Con Vault tanks have already been approved by fire EI IGINEERED ";, '
n �• �, I I i;e;a� �-�rN f k�h rr .
officials in many local jurisdictions. Over 6,000 ConVault FOR SAFETY �,�"�I f ��'`� �•" �'�" `��u��,:��,, ,„Her„ r
AST Systems have been installed nationwide in the last six ! r _ ar
• ConVaults are engineered for tightness '` r .•;, roar
years,and are, in fact,currently in use in all regions of the �,,,., '� 't ._,° E I
j,,' '' Y ,.• integrity, utilizing patented manufacturing
county . ,. _ comvaf,ty b i
y' l'.• , ."-; << l,,, .,-c_:,\, • , , procedures. The result is a seamless six-inch i F`'"f11b"
■ Each Con Vault tank ispressure-tested and meets ,� - r •�-'r'"'"l° '''Al'' �""'
„ �� <:;, concrete vault which gives thermal protection ""'�, °, ,
NFPA 30 and 30A fire safety standards,and are fitted for "" A!, , .r minimizing temperature change for flammable
grounding per NFPA 78. •• '�.• l liquids stored in excessively hot or cold envir-
■ ConVault tanks have been certified by the California Air , 1 ' •_ `t - onrnents.The system contains no cold joints or ;. .�•�, "
•
Resources Board for Balanced phase 2 Vapor Recovery. ( I e; heat transfer points on the bottom or sides. ' , }
■ Primary steel tank and overfill containers bear UL labels : " • `e 'i+w ` .1. }= The monolithic shell also provides ballistic and1. '
and meet UL Standard 142. The special enclosure has , .;,WI' l k Y •" vehicle impact protection. -
•
been successfully exposed to a 2-hour liquid pool fire test ----- -------5 ' :•. _
by Underwriters' Laboratories of Canada (results availa- °
ble upon request). -________•- —__ ___