HomeMy WebLinkAboutDocumentation_Regular_Tab 10C_12/10/1992 ArlorillI Ow „„ VILLAGE OF TEQUESTA e���� ; ft WATER DEPARTMENT r`„ of ► ram Post Office Box 3474 • 357 Tequesta Drive Ch`_�"., y Tequesta, Florida 33469-0474 • (407) 57543230 Laserfiched MEMORANDUM: TO: Thomas G. Bradford, Village Manager FROM: Thomas C. Hall, Water System Manager lib DATE: December 3, 1992 SUBJECT: Diesel Fuel Storage As you are aware in this year' s budget, the Water Department has allocated $30,000 for upgrading our Diesel Fuel Storage tank at our Water Treatment facility -on Old Dixie Highway. Due to the strict regulatory requirements now in place, we must remove our old underground tank as we did behind Village Hall and replace it with a unit that meets today's standards. We intend to increase our fuel storage capacity from 500 to 1, 000 gallons, thereby allowing us to have an increase in fuel availability in times of emergency. Present tank capacity only provides sufficient fuel for our plant emergency generator to operate continuously for just under five days. This new tank will increase our emergency operation capability to almost ten days as well as being an additional supply source for our portable generator serving• our wellfields. On October 20, 1992, specifications for the above tank were mailed to the . attached contractor list requesting formal Bid Quotes. A Bid Tabulation is attached. I would like to recommend that the Village accept the quote from Glasgow Equipment Service, Inc. in the amount of $13, 845.00. This company also performed the previously mentioned tank removal and installation behind Village Hall . Please place this item on the Council agenda of December 10, 1992 for approval . TCH/mk Attachments . • Rv".,-4,1 P7ner 1, 000 GALLON DIESEL TANK CONTRACTOR LIST BID QUOTE Glasgow Equipment Service, Inc. 1750 Hill Avenue Mangonia Park, Florida 33407 Phone: ( 407 ) 842-7236 FAX: ( 407 ) 842-7402 $ 13, 845.00 PIECO, INC. 8105 W. 20th Avenue Hialeah, Florida 33401 Phone: (305 ) 558-0440 FAX: (305 ) 362-0820 $ 20, 926.84 Olympic Industries, Inc. P. O. Box 770 Palm City, Florida 34990 Phone: (407 ) 286-9319 $ .22, 445.00 Atec Associates, Inc. 3555 Fiscal Ct. Suite 9 West Palm Beach, Florida 33404 Phone: 844-1166 FAX: 844-7659 $ 14, 248.00 Missimer & Associates, Inc. 600 Sandtree Drive, Suite 101 Lake Park, Florida 33403 Phone: 775-6612 FAX: 775-6615 $ 26,456.00 Hydrocarbon Monitor & Environment 8414 South U. S. Highway 1 Port St. Lucie, Florida 34952 Phone (407 ) 468-4611 FAX: 489-5830 No Bid Slater. Corporation 4700 S.W. 51st St. , Building 202 Davie, Florida 33314 Phone: . (305 ) 791-0336 FAX: 791-0650 No Bid Underground Tank Specialties 5770 N. Military Trail West Palm Beach, Florida 33407 Phone: 686-4223 FAX: 640-0224 No Bid r � VILLAGE OF TEQUESTA L. ti, ' WATER DEPARTMENT rPost Office Box 3474 357 Tequesta Drive ' ' Tequesta. F orida 33489-0474 • (407) 575-8230 October 20 , 1992 Glascow Equipment Service , Inc . 1750 Hill Avenue Mangonia Park , Florida 33407 RE: Formal Quotation fdr 1 ,000 Gallons Convault Fuel Storage Tank Dear Contractor : The Village of Tequesta is requesting formal quotes within fifteen ( 15 ) days for the following: o Provide all . labor , equipment and materials to remove and properly dispose of one ( 1 ) 550 gallon steel underground Diesel Tank . o Furnish Organic Vapor Analysis testing on surrounding soil and water . o Provide D .E .R .M . and customer with written report . Backfill the excavation with clean fill and compact to finished grade . o Provide all labor , equipment , materials engineering , certifications , permits and fees to construct an 8 inch x 12 ft . x 6 '6' reinforced concrete slab . On the slab , furnish and install one ( 1 ) new 1 ,000 gallon above ground Convault Fuel Storage Tank . o Include with tank all fittings , vents , overfill and spill containment , fuel gauge and 20 year manufacturer 's warranty . Vendor must also supply verification of tank approval from all regulatory agencies having jurisdiction and tank must be UL approved . o Install double wall fiber glass piping from the tank to existing building and transfer of fuel from old tank to new tank . Contractor must be State Certified as a pollutant storage systems specialty contractor and be registered with the Village of Tequesta . It is realized that any excessively contaminated soil must be removed and properly disposed of at an additional cost . ,J 0 L/o: . >z- i - G Should you have any questions , please contact the undersigned at 575-6230 . Please direct your correspondence to my attention . Sincerely , • • Thomas C . Hall Water System Manager TCH/mk I r t 'i+V` SIDE VIEW int �� �, v TOP VIEW �. � �, .,,,,t...,,o,,,,;::„,„%‘.., 7:GALLON U.L.LISTED OVERFILL CONTAINMENT VENT EMERGENCY Millie. 11 MUill® t r ., d ��• dr , 4" NIPPLE -,WITH INTERNAL DRAIN AND POSITIVE SEAL f NIPPLE i 111 f 1 NIPPLE o ollira81111111. ' 6"Emergency Vent 2 # u ' ø27;=ll O THE LEADER IN AE�OVE-GROUND FUEL STORAGE,• 1. Leak Detector Tube 0 80001bs. �® 3,q„ D250 Gallon 12000 lbs. - . - 500Gnllnn ,2000lbs. CROSS SECTION - , - " _ .. -0500 Gallon 18000 lbs. '��� - _ . .. 1000 Gallon 18000 lbs. '®�� �'• . b ?;o; .I • _ - D1000 Gallon 30000 lbs. ®�® - - - - , - - ` 2000 Gallon 30000 lbs. I —P y - STEEL TANK i i as^I , - • - . ` - - n ;'''' S OOO Gallon 51000 lbs. 1.111111.. fl�Xi• -ii INSUlATION'I.750"1 i _' • �Xi ONES I30 MILL I" " - k WIRE MESH i 11') r - k' - ' - CONCRETE 16,0"1 1 N ,y „w• At last there is an environmentally safe and practical � r _ **� " r alternative for storing petroleum based products: Con- � ., 'a � , Vault's complete aboveground vaulted tank and fuelin s s- we " 4 .,d a 9 Y tern. Constructed of steel and housed in an attractive con- • �* . "f,. wi`�= '># :- t Crete vault, the unit offers secondarycontainment =' eft `: f s } r. ' state-of-the-art, cost-efficient way to meet your storage -` a-'�. 4 ter, . �q t ' "}; needs. `(t �i ` r t ,.s+ *e � : `�,„ aw r • k' r- a : ''r, ��i ^r t5 r • r ..4 , . S e '�' P �^� -. it �, •r"f '#J'wa �. r♦ • n, .,. tG?- 1 " a t:. Put the storage tank of choice to work fOryou — _,. "u � , .. �,. ; ` ',r • a e ,• a, ,. ConVault. U.S.PATENT'#4,$26,644;#4,9Dal,235;#4,934,122;#4,963„082; ,•� -- , . • #4,986,346(OTHER ti.S, FOREIGN PATS.PEND.) ° _ W -'�` ., F;' Y K r '1.6 • z,s a t r-- • m r -. ,L 3d `''I' . ',, 1.f' t l:r y r +" 4 _ 3'L. T '..et - - :'3.. a`s_w„ -� f '^ , '7. • 1_ ' 1a 4,k n a' a a s`t"777 `' -�' ,9' 4= E- -,1 11 - P s �944 4 tt fib .0;i 1= " :d) • I! _ i, d I - r J A ^� r � I FaO IDA iKd rdtl H �fT _ • ' 3 <;.1.,i':::;;;;.,;;. ...r,-;.,,..44.;,,,,,,,;;;.1: 1vstaiu tQ4JY�ilTtY'p ;;;;:::,4:::r*:°::!,f,C4stlt,.:7:..);':; �Jr A Y � F4Qfi1�A§' w x ° w ref s' -' .,. ': , MFO. IN W/LOW000 BY I. -:#� ,,,v*. ," x*.1, `. _ - - - 3 s "rh "°" 'M: 3.P Technical information with reference to '°"*' o-- �.oe'� C results t tanks and various test CO NVAU�� ,. . '* -.-"' '`�,"�' :. - - '= m ... W. al, 0.• can be obtained by writing Con- :. """ ��'q''� a .�.'r""'� -'•� ` �' � •n Vault. Always consult local fire and °^' .„T- .*nY,� ':-r � ';_ '�°; �'°'�,,,'=«*' 3 .- `'1 ''s"` ,‘-tiAa" , 'W` err , a " r ,i 4 «. . building codes before installinga Con- **mow••-!�',�- ' ^'w-"^�� "' "� ��r '' - Vault tank since environmental and rw.-...� s s. "�'°^._ ' rs� ' -M'* safety regulations can vary between f �- ., k "R:'-- --a,,, . r t - e s"' ` '"' .rv��..�d„ry� jurisdictions. Qc . :,,- _..-.. '� _ sc• - ,. _ - - --"''�- •, '�'.�¢ 7-800-642-154® � 743, "a"jr .ir'" .„..."'�'"e""� ^,:??x,,r,.,�r ;, ,r, s.- -& a"� C ma's x t ` y ? r: cam , .• c a y - - Z# �s r� .€ � �� to - ..4-g""'",w, ,.x=o P.O. Box 238 • 1410 Industrial Drive • IA9ildwtood� Florida 34785-0238 ,,. - :-. ..•, 14 ` ,,1�; . e4, ---,- •-: , ;:. ,. -.. Phone �804) 748-6462 • (800) 642-1540 or, FA)( I904) 748-6820 % '• '" �" I. '*z" { ` .a ,F; ,• •c;x a�` ... '^- ",a °J.•�:f• "` r a s" .. y. w«,.^• -it ^'rr. ..wr , - - "�� 'a, `Tw '3's `� p .— 'Gvk'wry�3...l„-., 'iF"t eo '4-y` ' , _ r "',S' S' 1 +.n_ ^F M I t' T I - r'1 ■ M 174'r },$,, 41Z, C C . m . , V LiIt : 1 - ;r g':R �g N/.'' �".`f.� . i7 t-- -- - R ) ter t NI l,1 2 i.ii." FORAS IiJISITIVE Iu*JVIRDDNMENT - ° St a. ¢ , 'k ,_C•HI fit. ,I* 1-- -1F:5- . 1 crVeit C8V.t4bL1=y Bltt-6 N�OI4IDA THE i ,x- -6 . CONVAULT ADVANTAGE �, Y Ili 3. ib: -, , ttritt.tz'1414." tot DESIGNED FOR VALUE .° ■The ConVault storage system often costs less than half ; * .: ' , r z . as much as comparable underground installations. The ` " '`' elimination of system design engineering alone can pay for '' r� the complete ConVault fueling system. Tank capacities . `� ' `' � THE ABOVEGROUND range from 125 gallons to 5,200 gallons and can be mani- SOLUTION TO THE folded for higher volumes. UNDERGROUND PROBLEM • ConVault tanks have a long life; each comes with a standard 20-year warranty. A 30-year warranty is / 1 ■ Nationwide interest in the preservation of our envir- o• nment has prompted all levels of government to issue optional. �:, f ' _ � <" 3 strict guidelines for the installation,operation and rem- ■ ConVault tanks are self-contained and portable. This oval of underground storage tanks(UST's).As a result, b allows for tank relocation or resale as your businessk .. -.. . ...; z ="` g owners may a faced with expensive upgrades,testing, requirements change. _ _ monitoring equipment and pollution liability insurance to • ConVault's complete fuel storage and dispensing sys- comply with these regulations.In the event of a leak,the tern is a finished unit when shipped. Units are manufac- actual costs for soil and groundwater clean-up can be tured under strict quality control standards,with no need - 5 catastrophic. for excavation, painting, assembly or completion. Addi- "`�� ray ''+ ��� �,,� t� � • ConVault's innovative vaulted aboveground storage tional expenses are limited to freight, the cost of a con- -," ',,I . h',t�' t„ a'' � ��' '''T " - ' tanks are the proven solution for these problems. The crete pad and electrical service if desired. • Con Vault patented system is designed for safety and ■ Leasing programs are available which offer flexible and ,, • value while complying with environmental and fire code attractive lease-to-own options for both commercial and regulations. government users. MEETS GOVERNMENT, ' tti" ENVIRONMENTAL AND FIRE SAFETY REGULATIONS y ;, '4 1.7, F- ■ ConVault tanks meet applicable safety requirements 5w �, K y- ' r , r; ` � � " :r' ' Y(,"i �iM �4,y • • 4 .�� U' jj yA j�/I£ a i L � f S� � for secondary containment, leak monitoring, and spill and � �� ��� o� ,?� - �, �,�: r 1 ;� -. overfill protections. .. �r:.;��,-'`��,. '� '(mot ..l n�-''•� �,� ,�f� �r-� 'a� rs .>tr�, �iz � �_f7 � {�-+. r/a' � $ d y'l f ' .,. T '4 ,�jt r7; f,;. r!� ■ Con Vault tanks have already been approved by fire EI IGINEERED ";, ' n �• �, I I i;e;a� �-�rN f k�h rr . officials in many local jurisdictions. Over 6,000 ConVault FOR SAFETY �,�"�I f ��'`� �•" �'�" `��u��,:��,, ,„Her„ r AST Systems have been installed nationwide in the last six ! r _ ar • ConVaults are engineered for tightness '` r .•;, roar years,and are, in fact,currently in use in all regions of the �,,,., '� 't ._,° E I j,,' '' Y ,.• integrity, utilizing patented manufacturing county . ,. _ comvaf,ty b i y' l'.• , ."-; << l,,, .,-c_:,\, • , , procedures. The result is a seamless six-inch i F`'"f11b" ■ Each Con Vault tank ispressure-tested and meets ,� - r •�-'r'"'"l° '''Al'' �""' „ �� <:;, concrete vault which gives thermal protection ""'�, °, , NFPA 30 and 30A fire safety standards,and are fitted for "" A!, , .r minimizing temperature change for flammable grounding per NFPA 78. •• '�.• l liquids stored in excessively hot or cold envir- ■ ConVault tanks have been certified by the California Air , 1 ' •_ `t - onrnents.The system contains no cold joints or ;. .�•�, " • Resources Board for Balanced phase 2 Vapor Recovery. ( I e; heat transfer points on the bottom or sides. ' , } ■ Primary steel tank and overfill containers bear UL labels : " • `e 'i+w ` .1. }= The monolithic shell also provides ballistic and1. ' and meet UL Standard 142. The special enclosure has , .;,WI' l k Y •" vehicle impact protection. - • been successfully exposed to a 2-hour liquid pool fire test ----- -------5 ' :•. _ by Underwriters' Laboratories of Canada (results availa- ° ble upon request). -________•- —__ ___