HomeMy WebLinkAboutAgreement_General_08/17/2009~HEALTH~
Charlie Crist
Governor
Ana M. Viamonte Ros, M.D., M.P.H.
State Surgeon General
CERTIFIED MAIL 7cca8 a~>o ~ooo ~t~9 s~6~
RETURN RECEIPT REQUESTED
NOTICE OF PERMIT ISSUANCE
In the Matter of an Application for Permit by:
Michael R. Couzzo, Jr.
Village Manager FILE NO.: 138296-036-WC
Village of Tequesta
PO Box 3474 PROJECT: RO Treatment Addition
Tequesta, FL 33469
Enclosed is Permit Number 160009-010-WC, issued to Michael R. Couzzo, Jr., Village Manager,
Village of Tequesta, Florida, to construct a modification to a community water system, issued
pursuant to Chapter 403, Florida Statutes (F.S.).
A person whose substantial interests are affected by this permit may petition for an administrative
proceeding (hearing) in accordance with Section 120.57, F.S. The petition must contain the
information set forth below and must be filed (received) in this Office, Division of Environmental
Health & Engineering, Palm Beach County Health Department, 901 Evernia Street, West Palm
Beach, Florida 33401. Petitions filed by the permit applicant and the parties listed below must be
filed within fourteen (14) days of receipt of this permit. Petitioner shall mail a copy of the petition to
the applicant at the address indicated above at the time of filing. Failure to file a petition within this
time period shall constitute a waiver of any right such person may have to request an
administrative determination (hearing) under Section 120.57, F.S.
The Petition shall contain the following information:
a. The name, address and telephone number of each petitioner, the applicant's name and
address, the Permit File Number and the county in which the project is proposed;
b. A statement of how and when each petitioner received notice of the Health Department's
action or proposed action;
c. A statement of how each petitioner's substantial interests are affected by the Health
Department's action or proposed action;
d. A statement of the material facts disputed by Petitioner, if any;
e. A statement of facts which petitioner contends warrant reversal or modification
of the Health Department's action or proposed action;
`~~,z~ PALM BEACH COUNTY HEALTH DEPARTMENT
2~', ~.-„~~ Post Office Box 29 / 800 Clematis Street, West Palm Beach, FL 33402
`' - s'- Alina M. Alonso, M.D., Acting Director
': YLAL]'la ..LPAHI'M@Y'f'
wvdw.pbchd.com
TELEPHONE (561) 837-5900 FAX (561) 837-5294
Page Two
f. A statement of which rules or statutes petitioner contends require reversal or modification
of the Health Department's action or proposed action; and
g. A statement of the relief sought by petitioner, stating precisely the action petitioner wants
the Health Department to take with respect to the action or proposed action.
If a petition is filed, the administrative hearing process is designed to formulate agency action.
Accordingly, the Health Department's final action may be different from the position taken by it in
this permit. Persons whose substantial interests will be affected by any decision of the Health
Department with regard to the application have the right to petition to become a party to the
proceeding. The petition must conform to the requirements specified above and be filed
(received) within fourteen (14) days of receipt of this notice, in this Office, Division of
Environmental Health & Engineering, at the above address of the Palm Beach County Health
Department. Failure to petition within the allowed time frame constitutes a waiver of any right such
person has to request a hearing under Section 120.57, F.S. and to participate as a party to this
proceeding. Any subsequent intervention will only be at the approval of the presiding officer upon
motion filed pursuant to Rule 62-5.207, Florida Administrative Code (F.A.C.).
This permit is final and effective on the date filed with Clerk of the Department unless a petition is
filed in accordance with the above paragraphs or unless a request for extension of time in which to
file a petition is filed within the time specified for filing a petition and conforms to Rule 62-103.070,
F.A.C. Upon timely filing of a petition or a request for an extension of time this permit will not be
effective until further Order of the Department.
When the Order (Permit) is final, any party to the Order has the right to seek judicial review of the
Order pursuant to Section 120.68, Florida Statutes, by the filing of a Notice of Appeal pursuant to
Rule 9.110, Florida Rules of Appellate Procedure, with this Office, Division of Environmental Health
& Engineering, Palm Beach County Health Department, 901 Evernia Street, West Palm Beach,
Florida 33401; and by filing a copy of the Notice of Appeal accompanied by the applicable filing
fees with the appropriate District Court of Appeal. The Notice of Appeal must be filed within thirty
(30) days from the date the Final Order is filed with the Clerk of the Department.
Executed in West Palm Beach, Florida, This 17th Day of August, 2009.
STATE OF FLORIDA
PALM BEACH COUNTY HEALTH DEPARTMENT
~-r~ /'Lt
Darrel J. Graziani, P.E., Environmental Administrator
Environmental Health & Engineering
800 Clematis Street
West Palm Beach, FL 33401
(561) 837-5900
CERTIFICATE OF SERVICE
The undersigned duly designated deputy agency clerk hereby certifies that this NOTICE OF
PERMIT ISSUANCE was mailed to the applicant by certified mail and copies mailed to all listed
persons before the close of business on August 17, 2009.
Clerk Stamp
FILING AND ACKNOWLEDGMENT
y~`pp ~ t~nvltont-~nta! NnaMt; rind ~ngineerir:.
4G1 EV~iY!S%x 4rEs~t
P. (~. fax ~~
W~~t Felm C3est;h, FL. 384tk%
FILED, on this date, pursuant to Section 120.52(7), Florida Statutes, with the designated
Department Clerk, receipt of which is hereby acknowledged.
~~ ~ ~
(Clerk) ( ate)
cc: Utility: N/A
Engineer-of-Record: William D. Reese, P.E.
Florida DEP: Jose Calas, P.E.
r~.ok~u.~ uei~:,.krsu:~< ~~r
HEALTI-
Charlie Crist
Governor
Ana M. Viamonte Ros, M.D., M.P.H.
State Surgeon General
PERMITTEE:
Michael R. Couzzo, Jr.
Village Manager
Village of Tequesta
P. O. Box 3474
Tequesta, FL 33469
ID No.: 450-1438
Perm it/Certification: 138296-036-W C
Date of Issue: 08/14/2009
Expiration Date: 08/13/2014
County: Palm Beach
Utility: Village of Tequesta
Project: RO Treatment Addition
This permit is issued under the provisions of Chapter(s) 403, Florida Statutes, and Florida
Administrative Code Rule(s) 62-550, 62-555 & 62-560. The above named permittee is hereby
authorized to perform the work or operate the facility shown on the application and approved
drawing(s), plans and other documents attached hereto or on file with the department and made a
part hereof and specifically described as follows:
Construct: A modification to an existing community water system to increase capacity of the
existing reverse osmosis treatment train. The modification includes the following:
One Floridan Aquifer wellhead, R.O. Well #4, equipped with a horizontal pump rated
for 1111 gpm at 96 feet TDH and all required appurtenances, one 1.2 MGD
membrane train with 40 pressure vessels equipped with membrane elements
operating at a 75% recovery rate, one membrane feed pump rated for 1110 gpm at
675 feet TDH, one 3 micron cartridge filter rated for 1290 gpm, one 9' diameter
degassifier rated for 2.4 MGD, one two stage scrubber, pretreatment acid feed
piping modification, one sodium hypochlorite feed pump rated for 450 gpd and
associated electrical, instrumentation, and controls.
The proposed modification will increase the system maximum daily flow capacity to
6.3 MGD with the reverse osmosis plant increased to 3.6 MGD and the existing
greensand softening plant rated at 2.7 MGD.
In Accordance With: Application Form DEP 62-555.900(1), preliminary design report and plan
sheets 1-23, E01-E04 and 101-104 received June 18t" 2009, engineer's letter dated
July 28, 2009, and additional information received August 14, 2009.
Located at: Old Dixie Highway in Tequesta, Florida.
To Serve: Existing and future connections.
Subject To: General Conditions 1 - 15 and Specific Conditions 1 - 8.
~~~ ~~v~~~ PALM BEACH COUNTY HEALTH DEPARTMENT
~' ~- ~~; Post Office Box 29 / 800 Clematis Street, West Palm Beach, FL 33402
-~ _4~' ~ Alina M. Alonso, M.D., Acting Director
urnnrxiiv
www.pbchd.com
TELEPHONE (561) 837-5900 FAX (561) 837-5294
PERMITTEE:
Michael R. Couzzo, Jr.
Village Manager
GENERAL CONDITIONS:
ID No.: 450-1438
Permit/Certification No.: 138296-036-WC
Date of Issue: 08/14/2009
Expiration Date: 08/13/2014
The terms, conditions, requirements, limitations and restrictions set forth herein are "Permit
Conditions" and as such are binding upon the permittee and enforceable pursuant to the
authority of Section 403.161, 403.727, or 403.859 through 403.061, Florida Statutes. The
permittee is hereby placed on notice that the Department will review this permit periodically
and may initiate enforcement action for any violation of the "Permit Conditions" by the
permittee, its agent, employees, servants or representatives.
2. This permit is valid only for the specific processes and operations applied for and indicated in
the approved drawings or exhibits. Any unauthorized deviation from the approved drawings,
exhibits, specifications, or conditions of this permit may constitute grounds for revocation and
enforcement action by the department.
3. As provided in Subsections 403.087(6) and 403.722(5), Florida Statutes, the issuance of this
permit does not convey any vested rights or any exclusive privileges. Nor does it authorize any
injury to public or private property or anyinvasion of personal rights, nor any infringement of
federal, state or local laws or regulations. This permit does not constitute a waiver of any other
Department permit that may be required for other aspects of the total project which are not
addressed in the permit.
4. This permit conveys no title to land or water, does not constitute state recognition or
acknowledgment of title and does not constitute authority for the use of submerged lands
unless herein provided and the necessary title or leasehold interests have been obtained from
the State. Only the Trustees of the Internal Improvement Trust Fund may express state
opinion as to title.
5. This permit does not relieve the permittee from liability from harm or injury to human health or
welfare, animal, plant or aquatic life or property and penalties therefore caused by the
construction or operation of this permitted source, nor does it allow the permittee to cause
pollution in contravention of Florida Statutes and Department rules, unless specifically
authorized by an order from the Department.
6. The permittee shall at all times properly operate and maintain the facility and systems of
treatment and control (and related appurtenances) that are installed or used by the permittee
to achieve compliance with the conditions of this permit, as required by Department rules. This
provision includes the operation of backup or auxiliary facilities or similar systems when
necessary to achieve compliance with the conditions of the permit and when required by
Department Rules.
7. The permittee, by accepting this permit, specifically agrees to allow authorized Department
personnel, upon presentation of credentials or other documents as may be required by law,
access to the premises, at reasonable times, where the permitted activity is located or
conducted for the purpose of:
a. having access to and copying any records that must be kept under the conditions of the
permit;
b. inspecting the facility, equipment, practices, or operations regulated or required under this
permit; and
2
PERMITTEE:
Michael R. Couzzo, Jr.
Village Manager
GENERAL CONDITIONS: 7 (cont'd)
ID No.: 450-1438
Permit/Certification No.: 138296-036-WC
Date of Issue: 08/14/2009
Expiration Date: 08/13/2014
c. sampling or monitoring any substances or parameters at any location reasonably
necessary to assure compliance with this permit or Department rules.
Reasonable time may depend on the nature of the concern being investigated.
8. If for any reason, the permittee does not comply with or will be unable to comply with any
condition or limitation specified in this permit, the permittee shall immediately notify and provide
the Department with the following information:
a. a description of and cause of noncompliance; and
b. the period on noncompliance ,including exact dates and times; or, if not corrected, the
anticipated time the noncompliance is expected to continue, and steps being taken to
reduce, eliminate, and prevent recurrence of the recurrence of the noncompliance.
The permittee shall be responsible for any and all damages which may result and may be
subject to enforcement action by the Department for penalties or revocation of this permit.
9. The permittee agrees to comply with changes in Department rules and Florida Statutes after a
reasonable time for compliance, provided however, the permittee does not waive any other
rights granted by Florida Statutes or Department rules.
10. The permittee agrees to comply with changes in Department rules and Florida Statutes after a
reasonable time for compliance, provided however, the permittee does not waive any other
rights granted by Florida Statutes or Department rules.
11. This permit is transferable only upon department approval in accordance with Florida
Administrative Code Rules 62-4.12 and 62-30.30, as applicable. The permittee shall be liable
for any noncompliance of the permitted activity until the transfer is approved by the
department.
12. This permit is required to be kept at the work site of the permitted activity during the entire
period of construction or operation.
13. This permit also constitutes:
() Determination of Best Available Control Technology (BACT)
() Determination of Prevention of Significant Deterioration (PSD)
() Certification of Compliance with State Water Quality Standards
(Section 401, PL 92-500)
() Compliance with New Source Performance Standards
3
PERMITTEE:
Michael R. Couzzo, Jr.
Village Manager
GENERAL CONDITIONS:
ID No.: 450-1438
Permit/Certification No.: 138296-036-WC
Date of Issue: 08/14/2009
Expiration Date: 08/13/2014
14. The permittee shall comply with the following monitoring and record keeping requirements:
a. Upon request, the permittee shall furnish all records and plans required under department
rules. The retention period for all records will be extended automatically, unless otherwise
stipulated by the department, during the course of any unresolved enforcement action.
b. The permittee shall retain at the facility, or other location designated by this permit records
of all monitoring information (including all calibration and maintenance records and all
original strip chart recordings for continuous monitoring instrumentation), copies of all
reports required by this permit and records of all data used to complete the application for
this permit. The time period of retention shall be at least three (3) years from the date on
the sample, measurement, report or application unless otherwise specified by department
rule.
c. Records of monitoring information shall include:
-the date, exact place, the time of sampling or measurements;
-the person responsible for performing the sampling or measurements;
-the date(s) analyses were performed;
-the person responsible for performing the analyses;
-the analytical techniques or methods used; and
-the results of such analyses.
15. When requested by the department, the permittee shall, within a reasonable time furnish any
information required by law which is needed to determine compliance with the permit. If the
permittee becomes aware that relevant facts were not submitted or were incorrect in the permit
application or in any report to the department, such facts or information shall be submitted or
corrected promptly.
SPECIFIC CONDITIONS:
1. The permittee is responsible for retaining a Florida registered professional engineer as the
engineer of record for this project and upon completion, the engineer shall inspect for complete
conformity to the engineering report as approved.
2. Upon completion of construction, but prior to placing the system into service, a letter of release
must be obtained from the Palm Beach County Health Department; the documentation listed
below must be submitted for the letter of release:
a. A certification by the engineer that the project has been completed in substantial
conformance with approved engineering report. Certification to such inspection on DEP
Form 62-555.910(9) shall be provided to the Palm Beach County Health Department.
4
PERMITTEE:
Michael R. Couzzo, Jr.
Village Manager
SPECIFIC CONDITIONS: (2 cont'd)
ID No.: 450-1438
Permit/Certification No.: 138296-036-WC
Date of Issue: 08/14/2009
Expiration Date: 08/13/2014
b. One (1) set of record drawings of the completed project. Deviations from the original
approved design report are to be noted for the department's review.
c. Bacteriological results -Satisfactory bacteriological results for clearance of the wellhead,
associated piping, and raw water mains shall be two (2) consecutive daily samples with
results indicating an absence of coliform. The detailed procedure for bacteriological
clearance and release of systems for use is outlined in Technical Memorandum 07-1 PR, a
copy of which can be furnished upon request.
d. The well shall be cleaned, disinfected and bacteriologically cleared in accordance with
Chapter 62-555.315(6), F.A.C. Prior to sampling for bacteriological clearance, the well shall
be thoroughly pumped until no trace of the disinfecting agent can be found. Daily samples
for twenty (20) or more consecutive work-days shall be collected after pumping the well on
each consecutive day for fifteen (15) minutes at the rated capacity of the permanent pump.
Samples shall be analyzed for the presence of total residual chlorine, total coliform, and E.
Co/i. Testing for total residual chlorine shaA be performed following appropriate procedures
in the DEP Standard Operating Procedures for Field Activities, DEP-SOP-001/01. The
samples shall be handled in accordance with acceptable methods as stated in "Standard
Methods for the Examination of Water and Wastewater, 20th Edition, 1998". The detailed
procedure for bacteriological clearance and release of system for use is outlined in
Technical Memorandum 03-1 PR, a copy of which can be furnished upon request.
e. As a community water system chemical analysis of raw water for nitrate, nitrite, primary and
secondary inorganics, volatile organics, pesticides and PCBs, turbidity, and radionuclides as
required by Chapter 62-550, F.A.C. shall be submitted to the Department prior to release for
use. Only those parameters for which maximum contaminant levels were exceeded in the
raw water need to be analyzed for in the finished water.
3. This construction permit is issued with the understanding that pipe material and appurtenances
used in this installation will be in accordance with the latest applicable AWWA & NSF
Standards for public water supply.
4. All concrete coatings/admixtures, liners, grouts, protective paints and coatings shall be in
conformance with ANSI/NSF Standard 61-2002 and deemed acceptable for contact with
potable water.
5. All chemicals added to the system shall be in conformance with ANSI/NSF Standard 60-2002.
The maximum dosage shall not exceed the rate recommended by NSF In their report.
6. Prior to construction, all required permits or approvals must be obtained for all aspects of the
project from the appropriate agencies.
7. This permit only covers the specific items addressed in the applicant's permit application
package. Other existing system components were not reviewed for compliance with current
standards and issuance of this permit does not certify that those components meet current
standards.
5
PERMITTEE:
Michael R. Couzzo, Jr.
Village Manager
SPECIFIC CONDITIONS:
ID No.: 450-1438
Permit/Certification No.: 138296-036-WC
Date of Issue: OS/i~l~ Zoa9
Expiration Date:a8~/3~20/5~
8. One replacement motor for the membrane feed pumps shall be maintained for backup.
ISSUED THIS ~ °p DAY OF AUGUST, 2009.
PALM BEACH COUNTY HEALTH DEPARTMENT
STATE OF FLORIDA
A ma M. Alonso, M.D., Ast+~-Director
Palm Beach County Health Department
6